YB-12 series pre-installed transformer (European box-type substation)
YB-12 series pre-installed substations comply with GB17467-1998 High-voltage/Low-voltage Prefabricated Substation and IEC1330 standards, etc. This series of substations is mainly a perfect distribution device composed of four parts: shell, transformer, low voltage switchgear and high voltage switchgear. Because of its small size, compact structure, small occupied area and convenient relocation, it greatly shortens the capital construction cycle, reduces the occupied area and reduces the capital construction cost.
Key words:
Category:
Detail
Product overview:
YB-12 series pre-installed substations comply with GB17467-1998 High-voltage/Low-voltage Prefabricated Substation and IEC1330 standards, etc. This series of substations is mainly a perfect distribution device composed of four parts: shell, transformer, low voltage switchgear and high voltage switchgear. Because of its small size, compact structure, small occupied area and convenient relocation, it greatly shortens the capital construction cycle, reduces the occupied area and reduces the capital construction cost.
At the same time, the box-type substation is simple to install on site, quick to supply power, simple to maintain, and no special person is needed to be on duty. Especially, it can go deep into the load center, which is very important to reduce the power loss with the improvement of power supply quality, enhance the reliability of power supply and transform the distribution network. Box-type substation can complete the functions such as electric energy exchange, distribution, transmission, measurement, compensation, system control, protection and communication, etc. It is very suitable for power distribution in rural areas, towns, urban areas, building construction and factories.
Technical parameter:
Name | Unit | Data | |
High voltage part |
Rated voltage (kV) |
KV | 6/6.3/10/10.5 |
Rated frequency |
Hz | 50 | |
Maximum operating voltage |
KV | 6.9/11.5 | |
Power frequency withstand voltage (to ground and phase to phase/isolation fracture) |
KV | 32/36 42/48 | |
Lightning impulse withstand voltage (to ground and phase to phase/isolation fracture) |
KV | 60/70 75/85 | |
Rated current |
A | 400 630 | |
Rated short-time withstand current |
KA | 12.5(2S) 16(2S) | |
Rated peak withstand current |
KA | 32.5 40 | |
Low pressure part |
Rated voltage (kV) |
V | 380 220 |
Rated current of main circuit |
A | 100~3200 | |
Rated short-time withstand current |
KA | 15 30 | |
Rated peak withstand current |
KA | 30 63 | |
Branch current |
A | 10~800 | |
Number of branch circuits |
road |
1~12 | |
Compensation capacity |
Kvar | 0~360 | |
Transformer part |
Rated capacity |
KVA | 50~2000 |
Short circuit impedance |
% | 4 6 | |
Tapping scope |
±2x2.5% ±5% | ||
Connection group |
Dyn11 Yyn0 |
Product inquiry
Related products
Contact us
Tel:+86-371-55033377
Fax:+86-371-55033377
Email:hnyuhe@vip.126.com
Factory address: North Section of Xueyuan Road, Luoxin Industrial Cluster Area, Luoyang City
Social media

Mobile terminal
Copyright©Henan Yu He Electrical Co., Ltd.
This website already supports IPV6 Business license Powered by www.300.cn | SEO
SAF Coolest v1.3 设置面板 PBISS-ANSZ-YSZSE-WXV
无数据提示
Sorry,当前栏目暂无内容!
您可以查看其他栏目或返回 首页